Question:I want to change the CAN termination resistance setting on FC839-S2(UCOP).

Start the remote controller (AZ490) and switch to the Parameter Table 2 screen. (You will be asked for a password to access the screen. Enter "AF200".)

By changing the value of bits 4 and 5 of address 0CFH, the CAN termination resistance can be set.

The definition of the setting value is as follows.

00H: Termination resistance 120 Ohm
01H: Termination resistance 60 Ohm
10H: No terminating resistor

If you change the value on the screen and press the [OK] button, the parameter information in the card (current YIM folder) will be updated.

Example: When the value of 0CFH is changed from 08H to 18H, the termination resistance changes from 120 Ohm to 60 Ohm.


* Terminating resistance changes when the parameter setting is changed and the next device function (EPR command, etc.) is executed.

 